UL-300/NFPA/Ansul Manufacturer Deficiency: (6) Non-UL-300 Two-Piece Obsolete Nozzles During the inspection of the fire suppression system, the technician noted that the nozzles protecting the cooking equipment no longer meet the requirements of ANSI/NFPA/UL300 and the manufacturer, Ansul. Ansul no longer covers two-piece, pre UL-300, fire suppression nozzles and requires them to be replaced with the UL-300 approved Ansul nozzles. 10.2.3* Automatic Fire-Extinguishing systems SHALL comply with ANSI/UL300 or other equivalent standards and SHALL be installed in accordance with the requirements of the listing. As of 2014, standards written by the National Fire Protection Association (NFPA), and adopted by most states as a part of their fire code, require all kitchen systems must be UL 300-compliant. Additionally, most insurance companies also require compliance with this standard as a prerequisite to coverage. Nelbud proposes to install (6) UL-300-approved Ansul nozzles to keep the suppress